AUDIBLE VISIBLE WARNING SYSTEMS

MODEL CPS – 

Commercial Protector System® for Mechanical Operators
Emitter-Receiver Type Photo-Electric ControlThe Commercial Protector System® provides protection on doors up to 30 feet wide. Contains emitter, receiver, mounting brackets, and operator interface. 24VAC, use CPS-L if Solid State Logic 3 or Medium-Duty Logic Control Board unit.

OPEN only (all LiftMaster operators) after vehicle passes through infrared beam. Signal beam is projected across vehicle path and, when broken, sends a signal to open the door.


MODEL CPS-L

Commercial Protector System® for Logic 3.0 or Medium-Duty Logic Operators
Commercial Photo-Eyes

  • Industrial code technology
  • Durable steel brackets – floor or track mounting
  • Bright yellow safety color
  • Range up to 30 ft – indoor use only
  • Direct connect to all Logic 3.0, Medium-Duty Logic, ATS2113X, and LGO5011 commercial operators
  • Continuous self-monitoring system with added benefit of a timer-to-close feature

MODEL CPS3

Option Card with CPS-L Photo-Eyes for Applications Requiring Two Sets of Photo-Eyes
Provides a UL-approved self-monitoring system when installed with the CPS-L or CPS-LN4 second set of photo-eyes

  • Industrial code technology
  • Durable steel brackets – floor or track mounting
  • Bright yellow safety color
  • Range up to 30 ft – indoor use only
  • Direct connect to all Logic 3.0, Medium-Duty Logic, ATS2113X, and LGO5011 commercial operators
  • Continuous self-monitoring system with added benefit of a timer-to-close feature

MODEL CPS3-N4

Option Card with CPS-L Photo-Eyes with Nema 4 Enclosure for Apps Requiring Two Sets of Photo-Eyes
Provides a UL-approved self-monitoring system when installed with the CPS-LN4 second set of photo-eyes

  • Industrial code technology
  • Durable steel brackets – floor or track mounting
  • Bright yellow safety color
  • Range up to 30 ft – indoor use only
  • Direct connect to all Logic 3.0, Medium-Duty Logic, ATS2113X, and LGO5011 commercial operators
  • Continuous self-monitoring system with added benefit of a timer-to-close feature

MODEL CPS-RN4

Retro-Reflective Commercial Protector System® with Nema 4 Enclosure
  • Utilizes a sending/receiving retro-reflective photo-eye and a specially designed polarized reflector that increases obstruction detection reliability
  • Polarized photo-eye design for a safe retro-reflective photo-eye system
  • Designed as a normal open circuit, but not a self-monitoring system (does not incorporate industrial code technology)
  • Range up to 30 ft – indoor use only
  • 24VAC operation

MODEL CPS-N4 –

Commercial Protector System® with Nema 4 Enclosure for Mechanical Operators
Industrial-Duty Watertight Photo-Eyes

  • Provides the extra safety of a “non-contact” reversal
  • Range up to 45 ft
  • Bright yellow safety color
  • Heavy gauge metal mounting brackets – floor or track mounting
  • Quick installation and pre-molded for 1″ conduit
  • Patented electrical interface monitors system status at all times
  • LED indicators for quick alignment
  • Used on dual relay and contactor type commercial operators (N/O contact)

MODEL CPS-LN4

Commercial Protector System® with Nema 4 Enclosure for Logic 3.0 or Medium-Duty Logic Operators
  • Industrial code technology with Nema 4 enclosure
  • Durable steel brackets – floor or track mounting
  • Bright yellow safety color
  • Range up to 30 ft – indoor use only
  • Direct connect to all Logic 3.0, Medium-Duty Logic, ATS2113X, and LGO5011 commercial operators
  • Continuous self-monitoring system with added benefit of a timer-to-close feature

MODEL 3024161151

NEMA 4/12 Vehicle Loop Detector, 115V
Vehicle Loop Detector Outdoor Enclosure (NEMA 4/12)Watertight, oiltight enclosure with single 115VAC detector, wired to terminal block for field connection.

OPEN only (all LiftMaster operators) or SAFETY/HOLD OPEN only (operators with type B2, T, TS or T1 control wiring) when vehicle passes over loop wire. Requires a loop of wire embedded in the ground to connect to the detector. Requires 2-wire output connection to door operator and 115VAC power.


MODEL 302416241

NEMA 4/12 Vehicle Loop Detector, 24V
Vehicle Loop Detector Outdoor Enclosure (NEMA 4/12)Watertight, oiltight enclosure with single 24VAC detector, wired to terminal block for field connection.

OPEN only (all LiftMaster operators) or SAFETY/HOLD OPEN only (operators with type B2, T, TS or T1 control wiring) when vehicle passes over loop wire. Requires a loop of wire embedded in the ground to connect to the detector. Requires 2-wire output connection to door operator and 24VAC power.


MODEL 50102

Treadle Signal Hose
Treadle Signal Hose Outdoor Enclosure (NEMA 4/12)For additional hose above the 10 feet that is packaged with kits, or as replacement; good for indoor or outdoor use.

MODEL 503263

NEMA 1 Vehicle Loop Detector with Harness
Vehicle Loop Detector Indoor Enclosure (NEMA 1)Enclosed, requires separate 115VAC power. Wiring harness with plug for detector included.

OPEN only (all LiftMaster operators) or SAFETY/HOLD OPEN only (operators with type B2, T, TS or T1 control wiring) when vehicle passes over loop wire. Requires a loop of wire embedded in the ground to connect to the detector. Requires 2-wire output connection to door operator and 115VAC power.


MODEL 503267

Vehicle Loop Detector, 24V with Harness
Vehicle Loop Detector Indoor Enclosure (NEMA 1)

Enclosed, requires separate 24VAC power. Wiring harness with plug for detector included.OPEN only (all LiftMaster operators) or SAFETY/HOLD OPEN only (operators with type B2, T, TS or T1 control wiring) when vehicle passes over loop wire. Requires a loop of wire embedded in the ground to connect to the detector. Requires 2-wire output connection to door operator and 24VAC power.


MODEL 50800

RBMA Electric Treadle, NEMA 4/12
Electric Treadles Outdoor Enclosure (NEMA 4/12)Model RBMA five feet long.

OPEN only (all LiftMaster operators), or SAFETY only (LiftMaster operators with type B2, C2, L2, T, T1 or TS control wiring), after vehicle passes over treadle. The weight of the vehicle compresses an electric switch which sends an open signal to the door. Requires a 2-wire connection to the operator but does not require power to function.


MODEL 50ENL1218

Pave Over Pre-Formed Loop
Pre-formed Loop Outdoor Enclosure (NEMA 4/12)4′ x 8′ size, pave over style

Pre-formed flexible vehicle sensing loop with 50 feet of lead-in wire. For use with all vehicle loop detectors.


MODEL 50ENL1818

NEMA 4/12 Paver Over, Pre-Formed Loop
Pre-formed Loop Outdoor Enclosure (NEMA 4/12)4′ x 10′ size, pave over style

Pre-formed flexible vehicle sensing loop with 50 feet of lead-in wire. For use with all vehicle loop detectors.


MODEL 50HERK

Motion Detector
LiftMaster® motion detector opens after sensing an object.

  • Can be set up to detect vehicles separately from people and bring the two signals to two different outputs
  • Or, use the two outputs to differentiate between forward and backward movements
  • Detection fields are adjustable – manually or with a remote control
  • Can be mounted between 8.2′ up to 23′, with max range of 80′
  • Reference height of 23′ and angle of 45 degrees
  • Detection field is 20′ x 16′

NOTE: Requires 24-volt power supply separate from operator


MODEL 50HERKRC

Motion Detector Remote Control
Remote control for the LiftMaster® motion detector to conveniently choose from 8 different preset comfort functions, to adjust detection fields, mounting heights, relay hold interval, cross traffic optimization, direction recognition, people/vehicle separation, slow motion detection, turn on/off filter functions, open the door manually and much more.

  • Bidirectional
  • Fine-tune the motion detector from the ground without guessing if all the settings have been received by the sensor

MODEL 50XNL1218

NEMA 4/12 Saw-Cut, Pre-Formed Loop
Pre-formed Loop Outdoor Enclosure (NEMA 4/12)4′ x 8′ size, convenient “saw cut” style

Pre-formed flexible vehicle sensing loop with 50 feet of lead-in wire. For use with all vehicle loop detectors.


MODEL 50XNL1818

NEMA 4/12 Saw-Cut, Pre-Formed Loop
Pre-formed Loop Outdoor Enclosure (NEMA 4/12)4′ x 10′ size, convenient “saw cut” style

Pre-formed flexible vehicle sensing loop with 50 feet of lead-in wire. For use with all vehicle loop detectors.


SENSING EDGES

MODEL 50WSE

Electric Wireless Infrared Safety Edge Receiver Transmitter
Electric Edge TypeA wireless, infrared, supervised safety edge system eliminates the need for take-up reels or cords found on other safety edge products.

  • For use with rolling steel doors only
  • Kit includes receiver and transmitter
  • 3-volt battery for transmitter included

MODEL 50WSP

Pneumatic Wireless Infrared Safety Edge Receiver Transmitter
Pneumatic Edge Type A wireless, infrared, supervised safety edge system eliminates the need for take-up reels or cords found on other safety edge products.

  • For use with rolling steel doors onlyl
  • Kit includes receiver and transmitter
  • 3-volt battery for transmitter included

MODEL 50101

Exterior Air Switch with Metal Case
Sensing Edges Individual Pneumatic Comps.Exterior air switch with metal case, (N.O. contact).

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING.

2. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

3. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

4. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

5. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 50103

Air Hose 1/2IDX3/32WX100
Sensing Edges Individual Pneumatic Comps.Air hose, soft rubber

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING.

2. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

3. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

4. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

5. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 501012

Exterior Air Switch, SPDT
Individual Pneumatic Comps.

Exterior 3-wire air switch, (SPDT, plastic housing).

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING.

2. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

3. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

4. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

5. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 501031

Air Hose Plug
Sensing Edges Individual Pneumatic Comps.Air hose plug

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING.

2. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

3. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

4. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

5. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 655202

Pneumatic 14′ Sensing Edge with 2-Wire Take-Up Reel
Sensing Edges Pneumatic Kit

Pneumatic edge kit with exterior air switch. Includes 2-wire take up reel (20 feet extended) and 14 feet of air hose.A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

2. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

3. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

4. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 655302

Pneumatic 22′ Sensing Edge with 2-Wire Take-Up Reel
Sensing Edges Pneumatic Kit

Pneumatic edge kit with exterior air switch. Includes 2-wire take up reel and 22 feet of air hose.

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS II option board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

2. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

3. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

4. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 658202

Pneumatic 14′ Sensing Edge with 2-Wire Coil Cord
Sensing Edges Pneumatic KitPneumatic edge kit with exterior air switch. Includes 2-wire coil cord and 14 feet of air hose.

A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS IIoption board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

2. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

3. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

4. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


MODEL 658302

Pneumatic 22′ Sensing Edge with 2-Wire Coil Cord
Sensing Edges Pneumatic Kit

Pneumatic edge kit with exterior air switch. Includes 2-wire coil cord and 22 feet of air hose. For additional hose, add $1.50 per foot.A sensing edge should be used on every door for the protection of pedestrians and vehicles. Depending on the type of edge and type of control wiring of the operator with which it is used, the function of the edge will vary.

Standard Edge:
A standard 2-wire edge will cause a door to reverse when it meets an obstruction while closing if the operator has type B2, C2, S2, T, T1 or TS control wiring.

Failsafe Edge:
A failsafe edge (or self monitoring edge) requires either a 3- or 4-wire connection and will not only cause a door to reverse while closing but will also render the door inoperable if the edge is not installed or if it becomes damaged after installation. A failsafe electric edge requires an operator with type F2 wiring or the use of a CPS II™ option board. The infrared link-edge is inherently failsafe and requires only type B2, C2, S2, T, T1 or TS control wiring.

Important Notes:
1. SPECIFY LENGTH OF EDGE WHEN ORDERING. FOR ELECTRICAL EDGES, LENGTH EQUALS DAYLIGHT OPENING MINUS 2 INCHES. MINIMUM LENGTH – 5 FT.

2. A COIL CORD OR TAKE-UP REEL IS REQUIRED WITH ALL EDGES. SOME FAILSAFE APPLICATIONS MAY REQUIRE A 3- OR 4-WIRE CORD. Consult your LiftMaster sales representative.

3. TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.

4. IF DOOR IS OVER 22 FEET WIDE, ELECTRIC EDGES OR PHOTO EYES ARE HIGHLY RECOMMENDED.

WARNING: It is strongly recommended that some type of safety equipment be used with every door operator. Without safety equipment, serious injury or death may result!


SENSING EDGE CONNECTIONS

MODEL 50106

Take Up Reel, 2 Wire, 18 ga, 20 ft
Sensing Edge Connections Take-Up Reels Take-up reel, 2-wire, 18 ga., 20 ft. extended

Each sensing edge requires a means to connect it to the door operator. The means must be able to extend and retract as the door moves. Coil cords and take-up reels fulfill this function. A wireless connection may also be used.

IMPORTANT NOTE: TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.


MODEL 50107

Take Up Reel, 3 Wire, 18 ga, 20 ft
Sensing Edge Connections Take-Up Reels Take-up reel, 3-wire, 18 ga., 20 ft. extended

Each sensing edge requires a means to connect it to the door operator. The means must be able to extend and retract as the door moves. Coil cords and take-up reels fulfill this function. A wireless connection may also be used.

IMPORTANT NOTE: TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.


MODEL 501041

Coil Cord, 2-Wire, 18 ga, 20 ft
Sensing Edge Connections Coil Cords Coil cord, 2-wire, 18 ga., 20 ft. extended

Each sensing edge requires a means to connect it to the door operator. The means must be able to extend and retract as the door moves. Coil cords and take-up reels fulfill this function. A wireless connection may also be used.

IMPORTANT NOTE: TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.


MODEL 658200

Door Edge Connection Kit
Sensing Edge Connections Edge Connection Kit

Complete kit may be used with most sensing edges; kit includes two junction boxes – one for the door and one for the wall – a 3-wire coil cord (P/N 50 1042)

Each sensing edge requires a means to connect it to the door operator. The means must be able to extend and retract as the door moves. Coil cords and take-up reels fulfill this function. A wireless connection may also be used.

IMPORTANT NOTE: TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.


MODEL 5010730

Take Up Reel, 3 Wire, 18 ga, 30 ft
Sensing Edge Connections Take-Up Reels Take-up reel, 3-wire, 18 ga., 30 ft. extended

Each sensing edge requires a means to connect it to the door operator. The means must be able to extend and retract as the door moves. Coil cords and take-up reels fulfill this function. A wireless connection may also be used.

IMPORTANT NOTE: TAKE-UP REELS ARE NOT RECOMMENDED FOR USE WITH ANY FAILSAFE TYPE EDGE. USE COIL CORDS ONLY.


VEHICLE DETECTION SYSTEMS

MODEL K74-17750

Horn/Strobe
White horn/strobe

  • 115 volts
  • ADA compliant
  • Weatherproof

MODEL RDGRNCARD

Warning Device Option Board with Red/Green Light Box
Audible/Visible Warning Devices Option Board with Red/Green Warning Light Box

See Modifications at a Glance. Warning device option board with red/green light box for use only with the Logic Control Board (L3). Signals if door is moving or stationary. Other 120V or 24V signal devices can be attached. Signals red prior to door when CPS-LN4 or CPS-L timer function is used. NOTE: Activates down mid-stop. Down mid-stop allows door to stop at a mid-point from open position.

Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.


MODEL 4055

Trolley/Slide Caution Label
Warning Signs and Labels

CAUTION label for standard-lift sectional, slide and rolling doors

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 4065

Door Edge Caution Labels
Warning Signs and Labels

CAUTION label for high-lift and vertical lift sectional doors

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 402701

Moving Parts Caution Label
Warning Signs and Labels

CAUTION label regarding moving parts

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 406000

Pushbutton Warning Sign
Warning Signs and Labels

WARNING placard for placement near pushbutton

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 406009

Electrical Box Cover Caution Label
Warning Signs and Labels

CAUTION label for electrial box cover

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 406010

Disconnect Power Warning Label
Warning Signs and Labels

WARNING to disconnect power

These items are packed as standard in some or all LiftMaster door operators, depending on applicability. It is strongly recommended that they be replaced on installations where they have been lost or damaged.


MODEL 50500

Warning Light, 115V
Audible/Visible Warning Devices Warning Light

Wall mount warning light (bulb not included). 115V power required.

Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.


MODEL 50505A

Amber Light
Audible/Visible Warning Devices Colored Lights

Vaportight light with amber colored lens. Use up to 100 watt, 115VAC (bulb not included).

Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.


MODEL 50505G

Green Light
Audible/Visible Warning Devices Colored Lights

Vaportight light with green colored lens. Use up to 100 watt, 115VAC (bulb not included).

Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.


MODEL 50505R

Red Light
Audible/Visible Warning Devices Colored Lights

Vaportight light with red colored lens. Use up to 100 watt, 115VAC (bulb not included).

Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.


MODEL 50510

Alarm Bell, 4 in, 115V
Audible/Visible Warning Devices Warning Bell

6 inch alarm bell, wall mount. 115V power required.

NEMA1 Auxiliarly limit switches or auxiliary contact blocks to control warning devices may be added to the operator at the time of order (see door operator modifications) to allow for connection of warning devices. For further information, contact your LiftMaster sales representative.

WARNING: It is strongly recommended that audible/visible warning devices be included in every operator installation.